| Section 1 | Section 2 | Section 3 | Section 4 |
back to main Architecture page
2: PASSIVE SOLAR ARCHITECTURE - HEATING
Passive Solar Heating presents the most cost effective
means of providing heat to buildings. Generally,
the amount of solar energy that falls on the roof of a house is more than the
total energy consumed within the house. Passive solar applications, when
included in initial building design, adds little or nothing to the cost of a
building, yet has the effect of realizing a reduction in operational costs and
reduced equipment demand. It is reliable, mechanically simple, and is a viable asset to
a home. The following are rules of
thumb and an explanation of the essentials of passive solar design.
The mechanism of heating and cooling equipment is usually
referred to as a system. A building is designed (home, apartment house, etc.)
and a heating/cooling system using forced air equipment with air ducts; radiant
floors using hot water; etc., is specifically designed for it.
In passive building designs the system is integrated into the building
elements and materials - the windows, walls, floors, and roof are used as the heat
collecting, storing, releasing, and distributing system. These very same
elements are also a major element in passive cooling design but in a very
different manner. It should be
understood that passive solar design does not necessarily mean the elimination
of standard mechanical systems, although recent designs coupled high efficiency
back-up heating systems greatly reduce the size of the traditional heating
systems and reduce the amount of non-renewable fuels needed to maintain
comfortable indoor temperatures, even in the coldest climates.
The preceding explanations show that two elements must be
present in all passive solar heating designs:
a south facing exposure of transparent material (glass, plastic) to allow
solar energy to enter; and a material to absorb and store the heat (or cool) for
later use. With these two basic
elements in mind a number of approaches to designing a passive solar heated
structure are available. Passive
cooling is discussed elsewhere in this tutorial.
PASSIVE SOLAR DESIGN
The following section contains a brief description of basic
passive solar design approaches. Subsequent
sections contain more detailed information regarding each design and some
advantages and limitations of each. Do
not assume that because a particular design is more effective for a particular
purpose (i.e. water walls respond more quickly in the absorption and release of
heat) that it will serve in all climates and in all designs as the most
effective approach to passive solar heating or cooling.
Conversely, identified limitations do not mean that the approach is
ineffective, only that it is more appropriate and effective under specific
conditions. In choosing a
particular design approach, site and climate conditions must be evaluated
carefully so that the best approach or combination of approaches is
incorporated. No one passive design
approach is most advantageous in all climates or on all sites and situations.
In the building design industry there are certain ways of doing things
that have been developed over years of experience.
These are sometimes called rules of thumb (RT). The same is true of passive solar building design.
In the following sections, rules of thumb are identified for emphasis.
Keep in mind that these are simply guidelines that will, if observed,
produce favorable passive solar heating performance.
In some cases tables that give detailed information based on climate and
site variations supplement the rules of thumb.
DIRECT GAIN
The simplest of approaches is a direct gain design. Sunlight
is admitted to the space (by south facing glass) and virtually all of it is
converted to thermal energy. The walls and floor are used for solar collection
and thermal storage by intercepting radiation directly, and/or by absorbing
reflected or reradiated energy (Fig. 4). As long as the room temperature remains
high in the interior space storage mass (walls, floors) will conduct heat to
their cores. At night, when outside temperatures drop and the interior space
cools, the heat flow into the storage masses is reversed and heat is given up to
the interior space in order to reach equilibrium. This re-radiation of collected
daytime heat can maintain a comfortable temperature during cool/cold nights and
can extend through several cloudy days without "recharging".
Direct gain design is simple in concept and can employ a wide
variety of materials and combinations of ideas that will depend greatly upon the
site and topography; building location and orientation; building shape (depth,
length, and volume); and space use.
|
|
|
|
| Figure 4. Direct gain design - A direct gain design collects and stores heat during the day. At night stored heat is radiated into the living spaces. | Figure 5. Direct gain interior - A direct gain design with an interior water wall for heat storage. Heat stored in the water wall is radiated into the living space at night. |
A direct gain design requires about one-half to two-thirds of
the total interior surface area (RT) to be
constructed of thermal storage materials. These can include floor, ceiling and
wall elements, and the materials can range from masonry (concrete, adobe, brick,
etc.) to water (Fig. 5). Water contained within plastic or metal containment and
placed in the direct path of the sun's rays has the advantage of heating more
quickly and more evenly than masonry walls during the convection process. The
convection process also prevents surface temperatures from becoming too extreme
as they sometimes do when dark colored masonry surfaces receive direct
sunlight. The masonry heating problem can be alleviated by using a glazing
material that scatters sunlight so that it is more evenly distributed over
walls, ceiling, and floor storage masses (Fig. 6). This decreases the intensity
of rays reaching any single surface but does not reduce the amount of solar
energy entering the space.
![]() |
| Figure 6. Diffusing glazing materials. Translucent glazing scatters sunlight to all storage surfaces. |
INDIRECT GAIN
This passive solar design approach uses the basic elements of
collection and storage of heat in combination with the convection process. In
this approach, thermal storage materials are placed between the interior
habitable space and the sun so there is no direct heating. Instead a dark
colored thermal storage wall is placed just behind a south facing glazing
(windows). Sunlight enters through the glass and is immediately absorbed at the
surface of the storage wall where it is either stored or eventually conducted
through the material mass to the inside space. In most cases the masonry thermal
storage mass cannot absorb solar energy as fast as it enters the space between
the mass and the window area. Temperatures in this space can easily exceed 100°F.
This build up of heat can be utilized to warm a space by providing
heat-distributing vents the top of the wall (where the heated air, rising upward
due to less density, can flow into the interior space (Fig. 7). Vents at the
bottom of the wall allow cool air to be drawn into the heating space thereby
replacing the outflowing hot air, and picking up heat itself. The top and bottom
vents continue to circulate air as long as the air entering the bottom vent is
cooler than the air leaving the top vent. This is known as a natural
convective loop. At night the vents can be closed to keep cold air out and
the interior space is then heated by the storage mass, which gives up its heat
by radiation as the room cools. A variation of the vented masonry wall design is
one that employs a water wall between the sun and the interior space (Fig. 8).
Water walls used in this way need not be vented at top and bottom and can be
constructed in many ways - even 55-gallon drums filled with water, or specially
constructed plastic or sealed concrete containers. Again, as the water is
heated, the convection process quickly distributes the heat throughout the mass
and the interior space is warmed by heat radiated from the wall.
![]() |
Figure 7. Indirect gain Trombe wall stores heat during the day. Excess heat is vented to the interior space. At night Trombe wall vents are closed and the storage wall radiates heat into the interior space. | ![]() |
Figure 8. Indirect gain water wall collects and stores heat
during the day. Heat stored in indirect gain water wall is radiated into
the living space at night.
|
Another design approach (Fig. 9) takes advantage of the
greenhouse effect as well as the direct gain storage wall. A south facing
"greenhouse space" is constructed in front of a thermal storage wall
exposed to the direct rays of the sun. This wall would be at the rear of the
greenhouse and the front of the primary structure. The thermal wall absorbs heat
at the same time the interior space of the greenhouse is being heated. If a
vented masonry wall is used as storage, heat can also be released into the
living space by convection. This combination also works with an unvented water
wall. The greenhouse, then, is heated by direct gain while the living space is
heated by indirect gain (Fig. 10). The advantage is that a tempered greenhouse
condition can be maintained through days of no sun, with heating from both sides
of the thermal storage wall.
![]() |
![]() |
| Figure 9. Attached greenhouse with vented storage wall. Heat is stored in the wall during the day - excess heat is vented to the interior space. At night the wall vents are closed and stored heat is radiated to both the greenhouse and the interior space. | Figure 10. Attached greenhouse with water storage wall.
|
An indirect gain design which provides both heating and
cooling is the thermal pond approach, which uses water encased in
ultraviolet ray inhibiting plastic beds underlined with a dark color, that are
placed on a roof. In warm and temperate climates with low precipitation, the
flat roof structure also serves directly as a ceiling for the living spaces
below (Fig. 11) thereby facilitating direct transfer of heating and cooling for
the spaces below. In colder climes, where heating is more desirable, attic ponds
under pitched roof glazing are effective. Winter heating occurs when sunlight
heats the water, which then radiates energy into the living space as well as
absorbs heat within the water thermal mass for nighttime distribution. During
the summer, a reverse process, described later, occurs. For best effect, roof
ponds must be insulated (movable) so that heat will not radiate and be lost to
the outside. One of the major advantages of this approach is that it allows all
rooms to have their own radiant energy source with little concern about the
orientation of the structure or optimal building form.
![]() |
Figure 11. Heating cycle - Roof pond collects and stores heat during the day. At night roof ponds are covered and stored heat is radiated into the space below. |
ISOLATED GAIN
Finally, the isolated gain design approach uses a fluid (liquid or air) to collect heat in a flat plate solar collector attached to the structure. Heat is transferred through ducts or pipes by natural convection to a storage area - comprised of a bin (for air) or a tank (for liquid), where the collected cooler air or water is displaced and forced back to the collector (Fig. 12).
![]() |
Figure 12. Water or air convection loop. |
If air is used as the transfer medium in a convection
loop, heated air coming from the collector is usually directed into a rock (or
other masonry mass material) bin where heat is absorbed by the rocks from the
air. As the air passes its heat to the rocks it cools, falls to the bottom of
the bin and is returned to the collector completing the cycle. At night the
interior space of the structure is heated by convection of the collected radiant
energy from the rock bin. If water is the transfer medium, the process works in
much the same way except that heat is stored in a tank, and as hot water is
introduced, cooler water is circulated to the collector. In naturally occurring
convection systems (non-mechanically assisted) collectors must be lower than
storage units, which must be lower than the spaces to be heated (RT).
Of course, the addition of distribution assisting equipment can allow for
placement of system elements anywhere, but that would then be an Active Solar
System.
*PASSIVE SOLAR HEATING DESIGN CONSIDERATIONS:
SITE CONSIDERATIONS
The performance of any solar energy building, especially one
of a passive design, is strongly impacted by the site and the siting of the
building in relation to its surroundings. During the winter, the north side of a
building receives little direct solar impact due to shading from the winter sun,
which is low in the sky, while the south side is exposed to the benefits of
winter sun exposure. If site conditions are restricted, the passive solar heated
building location will be the area that receives the most sunlight between the
hours of 9:00 a.m. and 3:00 p.m. during the winter months. The building location
should be near at northern extremity of the sunny area so that future
development on properties to the south will not block access to winter sunlight.
This location also allows open space for winter activities or gardens to be
exposed to as much winter sun as possible.
BUILDING SHAPE AND ORIENTATION
Generally, buildings oriented along an east-west axis are
more efficient for both winter heating and summer cooling (RT).
This orientation allows for maximum solar glazing (windows) to the south for
solar capture for heating. This orientation is also advantageous for summer
cooling conditions since it minimizes east-west exposure to morning and
afternoon summer sunlight. This does not mean that all buildings must be rigidly
shaped oriented. Different building shapes and orientations can be designed to
perform efficiently by combining effective glazing, solar exposure, and shading
into the building form. This efficiency can be enhanced by variations in the
placement of interior spaces and by the use of such options as clerestories and
skylights. Depending upon the site, topography, and shape of the available
space, orientations other than east and west may be desirable. However, for most
climates, an east-west axis is the most efficient for both heating and cooling.
NORTH WALLS
In an east-west oriented building, a north facing exterior
wall will receive little sunlight during the winter and this will be a major
source of heat loss since heat always moves toward cold. Additionally, building
shading of north side open space usually renders it unusable for outdoor use. To
alleviate these situations the building should be shaped so that the roof slopes
downward from the south to the north wall. This reduces the height of the north
face of the building and therefore the area through which heat is lost. This
also allows sunlight to reach more area of north side outdoor spaces. Variations
of reducing heat loss conditions manifest in north walls include backing the
building into a sloped hillside or providing a berm, both of which reduce the
exposed north area. Both of these measures accomplish the purpose of a south to
north downward sloping wall (Fig. 13).
![]() |
| Figure 13. South to north downward sloping roof reduces heat loss from the north wall and allows sunlight to reach north side open space. |
INDOOR SPACE PLANNING
With location, orientation and shape of the building is the
consideration of interior space distribution. Habitable spaces that are most
occupied and have the greatest heating and lighting requirement should be
arrayed along the south face of the building. Rooms that are least used
(closets, storage areas, garages) should be placed along the north wall where
they can act as a buffer between high use living space and the cold north side
(Fig. 14).
![]() |
| Figure 14. Interior space should be arranged so that rooms with high heating and lighting requirements are arrayed along the south wall. |
ENTRYWAYS
Entries account for great deal of heat loss especially in
small structures. Heat is lost during opening and closing of doors (or windows).
Heat can also be lost by seeping between the doorframe and the door, and at
windows. This kind of window, door or other wall penetration heat loss (or heat
gain in the summer) is called infiltration. To reduce both direct and
infiltration losses, entryways should be recessed or protected against the
direct force of prevailing winds. Additional loss reduction can be accomplished
by providing an enclosed interior "air lock" space between an entrance
door and the main building. This double entry, or vestibule, creates a tempered
zone between the outside elements and the interior living space thereby reducing
the amount of warm air lost (and summer heat gained). It also reduces the amount
of cold or warm air entering the living space when the interior door is opened.
WINDOWS
The major expanse of windows in a passive solar energy
structure will be south facing solar windows. Whole design planning should
include considerations re: the impact of heat gain in the summer; views; natural
lighting; and privacy requirements in determining the placement and size of
windows in the structure.
For the most part, window areas on east, west and north
facing walls should be kept as small and as minimal as is consistent with
interior requirements and should be recessed and all should be double-glazed.
Windows are the least effective heat flow inhibitors of a building's shell, both
in terms of letting heat out in the winter, and letting heat in the summer. When
the outside temperature is 30°F and the inside temperature is 68°F, a square
foot of single pane glass will lose 20 times as much heat (about 43 BTU's per
hour) as a square foot of standard wood frame wall with 3'/z inches of
insulation.
DIRECT GAIN DESIGN
SOLAR WINDOWS
For Direct Gain heating the area of the glazed collecting
surface is determined in response to the duration and severity of winter
temperatures; the building size; and the amount of interior thermal storage
mass. A correct balance between these factors must be found in order to avoid
large daily temperature fluctuations that could result in overheating, even in
the winter. As a rule (assuming the correct amount of thermal storage mass),
0.19 to 0.38 square feet of south facing glass for each square foot of interior
floor area will provide enough sunlight to maintain an average temperature
between 65°F and 70°F during the winter months in cold climates (average
winter temperatures between 20°F and 30°F). In more moderate climes the same
temperatures can be achieved with 0.11 to 0.25 square feet of south facing glass
(average winter temperatures between 35°F and 40°F). More precise data is
given in Table 3. Location and sizing of glazing is also dependent upon the
building layout and types of spaces i.e., frequently used spaces vs.
infrequently used spaces. Adjustments in glazing size and location of solar
windows can occur by the use of reflectors, or when other passive solar design
elements are used in combination with a direct gain system such as heat loss
reduction by the use of movable insulation, double glazing, and by using wooden
sash and frames. The lower heat conductivity of wood can reduce the heat loss
around windows by as much as 20 percent.
CLERESTORIES AND SKYLIGHTS
Earlier it was mentioned that there may be considerations
that override the need for a large expanse of south facing windows in passive
heating designs. One is that interior room layout may affect the distance
between the collecting windows and the interior thermal storage mass wall.
Thermal storage masses in direct gain designs must receive direct sunlight
impact, and the farther away from the collecting surface they are, the taller
the collecting surface (glazing) must be in order to have sufficient surface
solar contact because of the sun's angle. This situation may produce intolerable
glare and overheating. Usually, storage walls should not be set back more than
1.25 to 1.5 times the height of the collecting surface - i.e. an interior
thermal storage wall should be no more than 12' from the 8' tall solar
collecting glazing wall. Also, direct sunlight may impact materials - i.e. dry
out wood furniture; discolor certain fabrics; etc. so care should be taken re:
interior decorating and maintenance. Finally,
and most important, adjacent structures and/or vegetation may reduce the amount
of direct sunlight to the point that a south facing collecting surface at ground
level becomes infeasible or seriously reduced.
Any one, or combination of these conditions make south wall
heat collection for direct gain problematic, but can be easily mitigated by the
use of clerestories or skylights. Both of these features admit sunlight at the
roof structure of a building and can be used to direct sunlight to a specific
interior surface. They can also be used in combination with or as a supplement
to a south facing glazed wall. Additionally, they provide for natural light
applications, which can reduce the need and cost of artificial lighting.
Clerestories are vertical south facing windows located at
roof level (Fig. 15). Their advantages are that they allow diffuse lighting into
a room; they provide privacy; and they can be placed almost anywhere on a roof.
In a compartmentalized building layout, each room can have its own source of
heat and light. They should be located at a distance from a thermal storage wall
that allows direct sunlight to hit the wall throughout the winter. This distance
is roughly 1.5 times the height of the wall. Ceilings in rooms containing
clerestories should be light in color to reflect or diffuse sunlight into the
living space. Large interior spaces
may have multiple clerestories arranged to allow maximum admission of sunlight.
Care must be taken that they do not shade each other, so the clerestorey roof
angle (from horizontal) of each clerestorey should be roughly the same angle of
the sun at its lowest winter point (noon on December 21).
Skylights are simply openings in a roof, which admit sunlight -they are
either horizontal (a flat roof) or pitched at the same angle as the roof slope.
In most cases. horizontal skylights are used with reflectors to increase the
intensity of solar radiation (remember the angle of incidence). Large skylights
should be provided with shading devices to prevent heat loss at night and heat
gain during the summer months (Fig. 16).
|
|
|
| Figure 15. Clerestory - clerestories can be used to provide sunshine onto interior walls which would normally not have a clear view of winter sunlight. | Figure 16. Skylights provide an alternative for direct solar gain, shading devices must be included as an integral part of the skylight to prevent overheating the space during mild periods. |
STORING HEAT – MASONRY
The major concern in designing a direct gain passive solar
structure to avoid uncomfortable temperature fluctuations over the day-night
cycle. It is relatively easy to calculate the amount of heat that will be
admitted to a room by any particular collecting surface. It is not, however,
easy to predict the percent of that heat which will be stored. Since the
difference between heat gained and heat stored will largely determine the
temperature fluctuation over a 24-hour period, this is one of the most important
design considerations. About 65 percent of all heat gained through solar windows
during a clear winter day can be lost during the night. This means that during
the day, 65 percent of the heat gained must be stored to offset nighttime
losses, and to maintain a relatively even temperature profile. Furthermore,
efficient storage during the day prevents the build-up of heat during daylight
hours.
In general terms, the following rules should be observed in
regard to design of heat storage systems:
* masonry and concrete floors, walls and ceilings to be used
for heat storage should be a minimum of 4 inches thick.
* sunlight should be distributed over as much of the storage
mass surface as possible by using translucent glazing. * a number of small
windows to admit sunlight in patches gives better control re: overheating.
* use light colored surfaces (non-thermal mass storage walls,
ceilings, floors) to reflect sunlight to thermal storage mass elements.
* thermal storage mass elements (floors, walls, ceilings)
should b dark in color.
* masonry floors used for thermal mass should not be covered
with wall-to-wall carpeting.
* direct sunlight should not hit dark colored masonry for
long periods of time.
Storing heat can be accomplished in many ways but the most
favorable storage occurs when each square foot of sunlight is spread (diffused)
over a nine square foot area of storage surface. With this distribution of
sunlight the storage mass need not be more than 4 inches thick. If sunlight is
distributed over less area, storage efficiency can be increased somewhat by
increasing the thickness of the storage mass- up to eight inches in thickness.
Increasing thickness beyond 8 inches has no beneficial effect on heat storage
efficiency. Therefore, the most efficient way to increase heat storage capacity
is to increase the storage surface area and the distribution of sunlight rather
than the thickness of the storage mass. This is because masonry absorbs heat
slowly, and intense sunlight on a small area will have a negative affect by
increasing room temperature while not significantly increasing the rate heat is
absorbed by the storage mass, while a system using dispersed, less intense
radiation across a larger surface of thermal mass storage will moderate room
temperature fluctuations and store most heat at the same time.
The heat retention efficiency of masonry storage masses is
also influenced by the kind of masonry used. Table 4 shows that magnesium brick
has twice the conductivity of the other materials listed. Higher conductivity
means that a material responds more quickly in both absorbing and giving up heat
- a quality that increases storage efficiency and decreases temperature
fluctuations.
![]() |
| Table 4. Thermal storage material properties. |
INTERIOR WATER WALLS
Because of the material's good convective properties,
interior walls of water (water walls) are much more efficient for thermal
collection, storage, and re-radiation than are masonry walls. Water walls should
be a dark color to increase heat absorption when exposed to direct sunlight, and
will perform well without the problem of heat build-up in the room. The
convection process carries heat away from the storage surface quickly,
preventing heat build-up, and allows the storage mass to heat evenly in a
relatively short time. Widely fluctuating interior temperatures are not often a
problem when interior water walls are used for heat storage.
If interior water walls receive direct sunlight between the
hours of 10:00 a.m. and 2:00 p.m. and are a
dark color, about one cubic foot of water is required for each square foot of
solar window to maintain comfortable temperatures during
winter months. Increasing the volume of water in this ratio to 3 cubic
fed of water will decrease daily temperature fluctuations by as much as 6°F.
INDIRECT GAIN DESIGN:
Properly sized, indirect gain thermal storage elements,
usually walls, can provide a high percentage of the heat required to keep a
space at comfortable temperatures, even in very cold climates. Thermal storage
walls, like interior storage walls, can be constructed of either masonry or
water. For masonry walls, between 0.43 and 1.0 square feet of south facing
double glazed solar window is needed for each square foot of floor area in
climates with average winter temperatures between 20°F and 30°F A smaller area
can be used (0.31-0.85) if water is the storage medium. In climates where the
average winter temperature is 35-F to 45°F, the figures are 0.22 to 0.6 for
masonry walls and 0.16 to 0.43 for water walls. Table 5 gives more precise
information.
![]() |
| Table 5. Sizing a thermal storage wall for different climatic conditions. |
THERMAL STORAGE WALL SIZE
Correct wall size varies with local conditions and climate;
the amount of insulation used; and the latitude of the building site. The first
two elements affect the rate of temperature loss from a space, which is
influenced by the amount of difference between outside and inside temperatures;
and how much insulation is used to slow that rate. Latitude is important because it affects the amount of solar
radiation received at the collecting surface on any particular day. For
instance, on a clear January day in Tulsa, Oklahoma, a square foot of collecting
surface will intercept 1883 BTU's while on the same day, a like amount of
surface located in Seattle will intercept only 1537 BTU's (assuming the same
slope for both surfaces). Local conditions aside, it is generally true that wall
size will need to be increased as one moves further north in latitude.
Other conditions that bear on wall size include obstructions
to solar radiation exposure, such as trees, structures, etc.. While unhampered
solar access will determine an optimal wall size, reduced or variable access to
the sun will require a larger wall area to compensate for reduced solar impact.
Sizing guidelines identified herein are based on providing enough heat on a
clear January day to maintain an average space temperature of 65 to 75°F over a
24-hour period. Since thermal storage walls are placed between the solar
collecting glazing and the interior space to be heated, overheating is less
problematic than with a direct gain design. Very cold climates, or where site
conditions allow less than recommended wall size, can benefit from the use of
reflectors, which bounce the sun's rays to the collection window, thereby
increasing the amount of solar radiation moving through the glazing and
intercepted by the energy absorber wall. Thermal wall size reduction can occur
by as much as 15% if substantial insulation is used at all other wall and roof
locations to reduce heat loss from the the building.
WALL DETAILS
Aside from the wall area and amount of exposure, the
thickness, type of material, and exposed surface color of a wall are main
considerations that determine the effectiveness of a wall in meeting the thermal needs of the structure's
occupants. In general, cold climate design benefits from dark, exterior surface
colors at the thermal storage wall.
A variation of the cold climate, indirect gain masonry
wall, which relies on absorption of solar energy at its face and radiation
of converted heat at its back, is the addition of vents at upper and lower wall
locations to provide convected heat to the interior space. Thermal storage wall
vents take advantage of the excessive heat build up between the glazing and the
surface of the storage wall (Table 7) which can easily exceed 100°F.
Venting the top and bottom of the wall of the living space allows trapped heated
air to move, rising (hot air is lighter than cold air) from the space between
the glazing and wall and flowing into the building interior through upper vents.
As warm air moves through the vents, cooler room air is drawn through the lower
vents, where it is warmed and rises to repeat the action. This convective
cycle directly warms the interior space at the same time heat is being
absorbed by the thermal mass of the wall, which will give up its heat to the
interior at a later time. This dual action is a benefit for direct heating as
well as delayed heating.
![]() |
|
| Table 6. Material and recommended thickness.
|
|
![]() |
|
| Table 7. Effect of wall thickness on space air temperature fluctuations. |
Convection can continue 2 to 3 hours after sunset due to the
heated exterior surface of the thermal storage wall, so it is important that
upper vents are closed when the exterior surface begins to cool. This action
prevents a reverse convection cycle, which removes heat from the space. Interior
space heating quality can be controlled by providing a movable reflective screen
across part or all of the exterior surface of the thermal wall. Vent sizing is
about two square feet for each 100 square feet of thermal wall wall surface,
equally distributed between top and bottom vents (Fig. 17).
![]() |
Figure 17. Masonry wall - Vent placement and sizing in mass wall should be as shown in the illustration. |
Appropriate wall thickness varies with the material used
(Table 6). Again, the idea is to provide comfortable conditions while avoiding
large and rapid temperature fluctuations. Table 7 gives an idea of the range of
temperature fluctuations for six different wall thicknesses constructed of five
different materials. Regardless of the material used, it can be expected that
while thick walls will produce both minimum and maximum temperatures at
different times of day than thin walls, due
to the additional time it takes heat to be conducted, their increased capacity
for assimilating and radiating heat will be much greater .
Water walls are slightly more efficient than masonry walls in
collection, retention and re-radiation of heat. They require different design
consideration i.e. containing the water in an effective, inexpensive and
esthetically pleasing way. There are a variety of water encasing systems ranging
from manufactured, elegant free standing cylinders and containers to
do-it-yourself systems of used, stacked drums, free-standing plastic cylinders,
and site-built tanks.
ATTACHED GREENHOUSES
An indirect gain heating system, using a green house
structure as a heat collector, is multi-purpose, practical and efficient. It
also requires the most rigorous design because of its multiple nature, which
affects sizing for space heating, creating ideal conditions for greenhouse
conditions, and accurately predicting performance for both. The attachment of a
greenhouse to the south side of a building enables the structure to benefit from
the normal, heat collecting greenhouse operation. The greenhouse collects heat
due to its solar exposure. This heat can be conducted through a thermal storage
wall separating house and greenhouse, or can be convected to the interior space
of the building. In this way the greenhouse serves both as a heat collector, and
a solarium for people and plants. Generally, in cold climates, a greenhouse
design would use between 0.65 and 1.5 square feet of south facing double glass
greenhouse collecting surface for each square foot of floor area in the adjacent
living space. In more moderate climates this can be reduced to 0.33 and 0.9
square feet. This should provide enough heat to keep the average temperature in
the adjacent space between 60°F and 70°F. More data are given in Table 8.
![]() |
|
| Table 8. Sizing the attached greenhouse for different climatic conditions. |
It is desirable for a solar greenhouse structure to be
recessed into the south facade of the building, thereby minimizing east and west
exposures, which have little effect on heat collection but can be a great source
of heat loss. Furthermore, heat transfer through the common wall between the
greenhouse and the living space is increased in this configuration (Fig. 18).
Greenhouses for heating purposes can be added to frame buildings to provide for
direct heat during winter days, but such buildings, without thermal storage
mass, do not have the ability nor capacity to store heat for use at night. Some
designs integrating greenhouses, adjust for nighttime heating by transfer of all
greenhouse heat to main building storage mass (floors, walls, etc.) for deferred
use at night. This only works in moderately cold climates, because very cold
climates require the residual heat collected by the greenhouse to keep it, and
its contents, from freezing at night.
The common wall between the greenhouse and the building
interior can be constructed of thermal mass materials (masonry, water, etc.).
The greenhouse side of common walls should be dark in color (better absorber)
and should receive maximum sunlight throughout the day. Wall vents and/or
operable windows can be used to allow heated air directly into the interior
space during the daytime.
Wall thickness should be same as that provided for in an
indirect gain (Trombe) wall. If water is used, its minimum thickness should be 8
inches (or 0.67 cubic feet for each square foot of south-facing glass).
Masonry walls cannot absorb and transfer heat as fast as a
greenhouse can collect it. As a result, temperatures in the greenhouse will
fluctuate as much as 60°F on a clear day. To dampen (level out) these
fluctuations, extra storage mass (such as masonry units or containers filled
with water) can be placed in the greenhouse. These act as an interior heat
dampening water wall (1 cubic foot of water for each square foot of south facing
glass will reduce temperature fluctuations 25°F to
29°F).
If water is used as the common wall between the greenhouse
and the living space, temperature fluctuations will be smaller, and if more than
the 0.67 cubic feet of water for each square foot of glass is used in the wall,
temperature fluctuations will be further reduced.
In cold climates, it may be advantageous to utilize a heat
storage, in the form of a rock bin, under the building or living space, which
would act as thermal storage of heat collected during the day. Heat transfer can
occur by natural convection if the building is terraced up a slope, or by use of
a fan, which would transfer heat to a rock bed located in a crawl space under
the floor of the structure (Fig. 19). The rock bed should spread across 75 to
100% of the floor area of the structure in cold climates, and 50 to 75% of the
floor area in moderate climates. Heat from the greenhouse should be directed
over the rock bed and a means of returning cold air from the bottom of the rock
bed to the greenhouse should be provided. If a terraced design is used, colder
air will naturally settle due to the convective loop cycle. About 1.5 to 3 cubic
feet of fist-sized rock is necessary in cold climates and .5 to 1 cubic feet in
temperate climates. Rock bin storage has also been used as a part of a cooling
system in warmer climes.
![]() |
![]() |
|
| Figure 18. By extending the end walls of an attached greenhouse, loss to the outside is reduced while the heat gains to the space are incresed. | Figure 19. Small fans (less than 0.25 H.P.) can be used to aid in the transfer of heat from collection space to more remote parts of the structure. |
ROOF PONDS
Roof ponds can be used both for heating during the winter
months and for cooling during the summer months. In this section only the
heating aspects of roof ponds will be discussed. Table 9 gives the ratios of
roof pond collecting surface for each square foot of floor area in the interior
space. It should be understood that this will vary depending on location,
exposure and local conditions. The lower ratio given in the table should be
adequate at lower latitudes while the higher ratio should be used at higher
latitudes (colder climates). For latitudes higher that 36° north, roof ponds
require greater solar gain exposure as well as greater protection from loss of
gained heat.
Table 9. |
The system is simple in concept. The roof pond approach
brings the differing building aspects of a building - roof, ceiling, heating (and cooling) system, and heat
distribution (does away with ducts) into one system. The roof ponds of contained
water are the heating (and cooling) unit. The roof/ceilings of the building act
as the structural support for the roof ponds; the "radiator" device
for evenly distributed heating of the spaces below; and as a waterproof roof
system providing protection from the elements. The movable insulation above the
ponds is the weather protection, heating/cooling system "manager" and
additional protection from the elements. Wintertime heating is comprised of
daytime opening the insulating roof layer to allow solar radiation to heat the
water beds; water bed warming heats the supporting structure which is also the
ceiling for spaces below; heated support structure radiates heat to the space.
At night the insulated roof panels close to contain heat gathered by the ponds
to continue heating the spaces below. Cooling strategies, discussed later, are
the opposite operation plus additional elements.
The sun in northern latitudes is at a lower angle with solar
radiation traveling through a greater mass of atmosphere, which reduces its
energy content by scattering and reflection. In this situation, increased area
of exposure or use of solar reflection can be used to increase roof pond
effectiveness. Additionally, in colder climates, the roof pond system benefits
from insulating covers to prevent nighttime losses. The most beneficial
insulation system is one that is multi-purpose
and movable, operating only twice a day to 1) expose the ponds for heat
collection, and 2) to cover the ponds to prevent heat loss at night. This
insulation system is also beneficial in the summer when the roof ponds must be
insulated to prevent summer heat gain. The movable insulation structure can
operate in a number of ways - rolling, hinged, etc.. In climates where snow is
likely, ponds can be placed in a solar attic below the sloping roof with south
facing glazing to allow solar gain, and the attic ceiling can be painted o a
reflective color or sheathed with a reflective material. To increase system
performance, glazing for cold climate solar ponds can be dual pane, or the ponds
can contain an upper layer inflated air cell.
Ceiling structural support for solar ponds (64#/cu. ft.)
include structural metal decking (excellent for thermal transfer to spaces
below) or thin reinforced concrete decks (more costly, less effective for direct
transfer of heat).
In constructing the support structure for roof ponds, the
clear span can be as much as 16 - 20 feet or more (for metal decking or
reinforced concrete), requiring intermediate structural beams and supports
depending on the layout of the interior space and the weight of the ponds and
insulating devices. This can be a complicated matter and it is recommended that
assistance be sought from a structural engineer prior to design.
It is important to provide a waterproof layer (membrane,
etc.) at the pond support system surface to provide protections during draining
of water for maintenance, and from water bed material failure and/or weather
impacts. The capability to drain
the ponds in an easy and non-damaging manner is important. The water should be
enclosed in ultra-violet light inhibiting (prevents degradation) plastic bags,
waterproof structural metal or fiberglass tanks which form the ceiling below.
The top of the water containment system must be transparent and the sides/bottom
a dark color. Insulation panels should be constructed so that they can be
tightly sealed when closed to prevent infiltration heat loss. In some
applications insulating panels can also serve as reflectors when open in order
to direct more solar to the ponds.
Heat is transferred from the roof ponds through the support
deck to the interior space below. The edges of the deck should be carefully
insulated to reduce heat loss. The underside of the support deck serves as an
interior ceiling, and all surfaces (including galvanized metal decking) should
be painted. Because the system provides a "radiant" ceiling it is
important that no insulation is used
between the root pond and the interior space. The one exception to this rule is
at the bathroom, which generates high humidity from showers and tubs. Here, an
uninsulated ceiling can result in condensation and drippage, so effective water
barriers and insulation are critical.
Thermal ponds are typically water filled (6 to 12 inches
deep) clear, ultraviolet inhibiting plastic bags. Care should be taken to choose
materials which do not degrade when exposed to sunlight and water, nor are
easily damaged from handing and local conditions. Temperature stratification in
the ponds is avoided by using a clear top and dark bottom. With this
configuration, sunlight will penetrate the water, be absorbed at the black
surface and heat from the bottom will cause a continual convection cycle effect
in the pond.
Finally, exposed pond tops should be sloped to drain. This
avoids heat loss caused by evaporative cooling of the ponds during. While not a
problem for waterbed "bags", this is a problem for more fixed types of
installations. (see Haggard, K., et
al., "Research Evaluation of a System of Natural Air Conditions."
National Technical Information Service, Springfield, VA 22161, Order Number PB-243498).
Insulating panels can take many forms and configurations
depending on local conditions and design (flat roof with exposed ponds in
temperate and desert settings; pitched roof with glazing in snow country), and
range from pivoting panels to horizontal, sliding panels constructed from
standard metal building construction systems - insulation of polyurethane foam
reinforced with fiberglass strands between aluminum skins placed within standard
or easily formed metal frames. Panel tracks and supports must be designed so
that the panel system (insulation and frames)
fit as tightly as possible when closed in order to prevent compromise of
the systems effectiveness. Without an effective seal system a great deal of heat
stored can be lost at night due to infiltration. .
COMBINING SYSTEMS
Many times it is desirable, or even necessary, to use more
than one passive heating design strategy. For instance, the use of a thermal
storage wall may block a beautiful view while a direct gain design in the same
south wall may create intolerable glare and have a tendency to overheat. In such
cases the two designs can be used side by side or in any other configuration (a
thermal storage wall on each side of a direct gain window). It is essential,
however, to properly size this combination in order to maintain quality control
and avoid undesirable temperature fluctuations. About 60 to 75% of the energy
striking the collecting surface of a direct gain window can be used in space
heating. On the other hand, only about 30 to 45% of the energy striking the
collecting surface of a thermal storage wall is transferred to the interior
space as heat. It can be seen that the approximate ratio in sizing this
combination would be one square foot of direct gain window equals two square
feet of thermal storage collecting surface. With these approximations in mind,
it should be a relatively easy matter to size various combinations of passive
solar designs.
Variation of roof pond designs make it impossible to present
a simple rule of thumb for integrating with other design approaches. However, by
reviewing the sizing techniques for the other systems and by knowing the
specific design of the roof pond system, an approximate ratio can be calculated.
CLOUDY DAY STORAGE
Even on cloudy days passive solar heating designs continue to
collect energy from diffused sunlight. However, this greatly reduced and diffuse
solar radiation usually does not provide enough energy to keep interior
temperatures at 70°F. Well designed thermal mass systems are sized to have
carryover capacity and when combined with some auxiliary heating systems,
provide for a comfortable environment for a number of cloudy days.
As a rule, direct gain systems can provide comfortable
conditions for 1-2 cloudy days if the collecting area is increased by 10-20%,
and the interior walls and floors are of solid masonry more than 8 inches thick.
If water walls are used in place of masonry, increase the amount of water to two
or three cubic feet for each square foot of south facing collecting area.
In climates where a number of consecutive sunny winter days
are common there is a concern for overheating. For example, average temperatures
with the above sizing may result in average interior temperatures of 74°F.
However, on cloudy days, if the interior temperature drops an average of
four degrees per day, comfortable conditions can be maintained for two days with
no additional heating needed.
Oversizing in very cloudy or foggy climates is not
recommended since thicker masonry takes a few days of sunshine to become fully
charged. In climates such as these, overly thick storage masses are likely to
result in under-heating problems. Glazed areas with minimum mass thickness
should be used so that the system can respond quickly when sun is available.
Indirect gain systems differ slightly when designing for one
or two cloudy days' storage. The collector area should be increased by 10 to
20%, and thermal storage walls of greater conductivity be used. If water walls
are used, one or more cubic feet of water should be used for each square foot of
collector area.
In indirect designs, if standard masonry wall material is
used for cloudy day storage., the
surface area of the wall should be increased instead of increasing masonry wall
thickness. This may increase
average daily temperatures, but overheating is easily mitigated by use of
insulating panels or curtains drawn across the interior of the wall to provide
temperature control. Built in ventilation systems can be used to control
overheating for both indirect gain and direct gain systems..
MOVABLE INSULATION
In all structures, the greatest amount of heat gain is lost
through glazing, either by conduction through the glass or by infiltration
around the window frame. All heat loss during the winter reduces the efficiency
of all heating systems including passive solar design, and where possible,
movable, tightly sealed insulation should be used to cut losses to a minimum.
The extent of heat loss under varying conditions of protection is given in Table
10.
![]() |
| Table 10. Conduction losses through single and double glazing with and without shutters for Boston1. |
The use of movable insulation can simply involve manually
operated panels that slide on a track across the glazed area, or be motor driven
and temperature activated (more expense but more consistent control). Mechanical
systems can be used to operate insulation difficult to reach manually. If the
building is unattended when insulation should be moved, automatic timers
connected to thermostats and/or light sensitive devices can operate, providing
appropriate operation of the system. Some machinations can include automatically
operated louvers, motor driven panels (roof ponds, etc.) and movable insulation.
Whatever the method used, an effective insulation system will greatly increase
the efficiency of passive solar designs.
REFLECTORS FOR PASSIVE SOLAR HEATING
If partial shading is problematic, collection of solar
radiation can be greatly enhanced by the use of reflecting devices.
Generally, horizontal reflector equal in width and one to two times the
height of the glazed opening in. length should be used for vertical (wall)
glazing. South sloping skylights, benefit from reflectors located above the
skylight at a tilt angle of roughly 100° from the slope of the roof (Fig. 20).
The reflector should be roughly equal to the length and width of the skylight.
Solar collection can be increased 30-40% when reflectors are used with either
vertical, horizontal, or sloping glazing. For greatest efficiency, the angle of
a reflector in relation to the collecting surface must be carefully selected.
Table 11 gives the proper reflector angle for skylights with varying degrees of
slope.
In some instances, reflecting surfaces can be used to direct
sunlight to an interior storage surface such as a water wall. Reflectors should
also be constructed so that they can be used to block heat gain in the summer.
Table 12 gives the reflecting properties of some surfacing materials.
![]() |
![]() |
| Table 11. Reflecting tilt-angles for south-facing skylights. | Table 12. Normal specular solar reflectance of various surfaces. |
SHADING
South facing glass can be a source of overheating during
summer months. The potential for overheating can be controlled by a roof
overhang carefully designed to shade the glass during the summer (sun higher in
the sky) but not block sunlight during the winter (lower in the sky), and by the
use of movable outside shading devices.
Overhangs should be equal in length to roughly one fourth the
height of the window opening in southern latitudes (36° NL) and one-half the
height of the opening in northern latitudes (48° NL).
The projection of the overhang that will be adequate (provide
100% shading at noon on June 21) at particular latitudes can be quickly
calculated by using the following formula:
Projection = window opening (height)/ F (see Table 13)
A slightly longer overhang may be desirable at latitudes
where this formula does not provide enough shade during August.
The usefulness of overhangs can be increased if they are
constructed so that they are adjustable. Adjustable overhangs can be rolled back
to admit sunlight on cold spring days. Trellised overhangs that support
deciduous vines (vines that lose their leaves in the winter) are another way to
block sunlight in the summer and admit sunlight in early spring. Retractable
awnings and adjustable louvers can also be useful shading devices.
Table 13. |
OUTSIDE INSOLATION
(OUT-SULATION)
Masonry wall exterior surfaces can lose large amounts of
heat. For example - to achieve an
insulation quality equal to 3.5 inches of fiberglass insulation, a concrete wall
would have to be 12 feet thick. To avoid masonry wall heat loss to the exterior,
it can be insulated on the outside. This "thermos bottle approach"
includes the walls and the perimeter of foundation walls. Typical application is
the addition of 1 to 2 feet of two-inch rigid waterproof insulation placed below
grade to prevent stored heat in floors and walls from being lost to the outside.
In sunny temperate winter climates south facing, dark colored masonry walls need not be insulated as heat gained during sunny days will offset nighttime heat loss.
| Section 1 | Section 2 | Section 3 | Section 4 |