Passive
Solar Architecture - Heating
Passive
Solar Heating presents the most cost effective means of
providing heat to buildings. Generally,
the amount of solar energy that falls on the roof of a house is more
than the total energy consumed within the house. Passive solar
applications, when included in initial building design, adds little
or nothing to the cost of a building, yet has the effect of
realizing a reduction in operational costs and reduced equipment
demand. It is reliable, mechanically simple, and is a viable asset to
a home. The following
are rules of thumb and an explanation of the essentials of passive
solar design.
The
mechanism of heating and cooling equipment is usually referred to as
a system. A building is designed (home, apartment house, etc.) and a
heating/cooling system using forced air equipment with air ducts;
radiant floors using hot water; etc., is specifically designed for
it. In passive building
designs the system is integrated into the building elements and
materials - the windows, walls, floors, and roof are used as the heat
collecting, storing, releasing, and distributing system. These very
same elements are also a major element in passive cooling design but
in a very different manner. It
should be understood that passive solar design does not necessarily
mean the elimination of standard mechanical systems, although recent
designs coupled high efficiency back-up heating systems greatly
reduce the size of the traditional heating systems and reduce the
amount of non-renewable fuels needed to maintain comfortable indoor
temperatures, even in the coldest climates.
The
preceding explanations show that two elements must be present in all
passive solar heating designs:
a south facing exposure of transparent material (glass,
plastic) to allow solar energy to enter; and a material to absorb
and store the heat (or cool) for later use.
With these two basic elements in mind a number of approaches
to designing a passive solar heated structure are available.
Passive cooling is discussed elsewhere in this tutorial.
PASSIVE
SOLAR DESIGN
(top)
The
following section contains a brief description of basic passive
solar design approaches. Subsequent
sections contain more detailed information regarding each
design and some advantages and limitations of each.
Do not assume that because a particular design is more
effective for a particular purpose (i.e. water walls respond more
quickly in the absorption and release of heat) that it will serve in
all climates and in all designs as the most effective approach to
passive solar heating or cooling.
Conversely, identified limitations do not mean that the
approach is ineffective, only that it is more appropriate and
effective under specific conditions.
In choosing a particular design approach, site and climate
conditions must be evaluated carefully so that the best approach or
combination of approaches is incorporated.
No one passive design approach is most advantageous in all
climates or on all sites and situations.
In the building design industry there are certain ways of
doing things that have been developed over years of experience.
These are sometimes called rules of thumb (RT). The same is true of passive solar building design.
In the following sections, rules of thumb are identified for
emphasis. Keep in mind
that these are simply guidelines that will, if observed, produce
favorable passive solar heating performance.
In some cases tables that give detailed information based on
climate and site variations supplement the rules of thumb.
DIRECT
GAIN
(top)
The
simplest of approaches is a direct gain design. Sunlight is admitted
to the space (by south facing glass) and virtually all of it is
converted to thermal energy. The walls and floor are used for solar
collection and thermal storage by intercepting radiation directly,
and/or by absorbing reflected or reradiated energy (Fig. 4). As long
as the room temperature remains high in the interior space storage
mass (walls, floors) will conduct heat to their cores. At night,
when outside temperatures drop and the interior space cools, the
heat flow into the storage masses is reversed and heat is given up
to the interior space in order to reach equilibrium. This
re-radiation of collected daytime heat can maintain a comfortable
temperature during cool/cold nights and can extend through several
cloudy days without "recharging".
Direct
gain design is simple in concept and can employ a wide variety of
materials and combinations of ideas that will depend greatly upon
the site and topography; building location and orientation; building
shape (depth, length, and volume); and space use.
|

|
|

|
| Figure 4. Direct gain design -
A direct gain design collects and stores heat during the day.
At night stored heat is radiated into the living spaces. |
|
Figure 5. Direct gain interior
- A direct gain design with an interior water wall for heat
storage. Heat stored in the water wall is radiated into
the living space at night. |
A
direct gain design requires about one-half to two-thirds of the
total interior surface area (RT) to
be constructed of thermal storage materials. These can include
floor, ceiling and wall elements, and the materials can range from
masonry (concrete, adobe, brick, etc.) to water (Fig. 5). Water
contained within plastic or metal containment and placed in the
direct path of the sun's rays has the advantage of heating more
quickly and more evenly than masonry walls during the convection
process. The convection process also prevents surface temperatures
from becoming too extreme as they sometimes do when dark colored
masonry surfaces receive direct sunlight. The masonry heating
problem can be alleviated by using a glazing material that scatters
sunlight so that it is more evenly distributed over walls, ceiling,
and floor storage masses (Fig. 6). This decreases the intensity of
rays reaching any single surface but does not reduce the amount of
solar energy entering the space.
 |
| Figure 6. Diffusing glazing
materials. Translucent glazing scatters sunlight to all
storage surfaces. |
INDIRECT
GAIN
(top)
This
passive solar design approach uses the basic elements of collection
and storage of heat in combination with the convection process. In
this approach, thermal storage materials are placed between the
interior habitable space and the sun so there is no direct heating.
Instead a dark colored thermal storage wall is placed just behind a
south facing glazing (windows). Sunlight enters through the glass
and is immediately absorbed at the surface of the storage wall where
it is either stored or eventually conducted through the material
mass to the inside space. In most cases the masonry thermal storage
mass cannot absorb solar energy as fast as it enters the space
between the mass and the window area. Temperatures in this space can
easily exceed 100°F. This build up of heat can be utilized to warm
a space by providing heat-distributing vents the top of the wall
(where the heated air, rising upward due to less density, can flow
into the interior space (Fig. 7). Vents at the bottom of the wall
allow cool air to be drawn into the heating space thereby replacing
the outflowing hot air, and picking up heat itself. The top and
bottom vents continue to circulate air as long as the air entering
the bottom vent is cooler than the air leaving the top vent. This is
known as a natural convective loop. At night the vents can be
closed to keep cold air out and the interior space is then heated by
the storage mass, which gives up its heat by radiation as the room
cools. A variation of the vented masonry wall design is one that
employs a water wall between the sun and the interior space (Fig.
8). Water walls used in this way need not be vented at top and
bottom and can be constructed in many ways - even 55-gallon drums
filled with water, or specially constructed plastic or sealed
concrete containers. Again, as the water is heated, the convection
process quickly distributes the heat throughout the mass and the
interior space is warmed by heat radiated from the wall.
Figure 7. Indirect gain Trombe wall
stores heat during the day. Excess heat is vented to the
interior space. At night Trombe wall vents are closed and the
storage wall radiates heat into the interior space.
|
|
Figure 8. Indirect gain water wall
collects and stores heat during the day. Heat stored in
indirect gain water wall is radiated into the living space at
night.
|
|
Another
design approach (Fig. 9) takes advantage of the greenhouse effect as
well as the direct gain storage wall. A south facing
"greenhouse space" is constructed in front of a thermal
storage wall exposed to the direct rays of the sun. This wall would
be at the rear of the greenhouse and the front of the primary
structure. The thermal wall absorbs heat at the same time the
interior space of the greenhouse is being heated. If a vented
masonry wall is used as storage, heat can also be released into the
living space by convection. This combination also works with an
unvented water wall. The greenhouse, then, is heated by direct gain
while the living space is heated by indirect gain (Fig. 10). The
advantage is that a tempered greenhouse condition can be maintained
through days of no sun, with heating from both sides of the thermal
storage wall.
 |
 |
| Figure 9. Attached greenhouse
with vented storage wall. Heat is stored in the wall during
the day - excess heat is vented to the interior space. At
night the wall vents are closed and stored heat is radiated to
both the greenhouse and the interior space. |
Figure 10. Attached greenhouse
with water storage wall.
|
An
indirect gain design which provides both heating and cooling
is the thermal pond approach, which uses water encased in
ultraviolet ray inhibiting plastic beds underlined with a dark
color, that are placed on a roof. In warm and temperate climates
with low precipitation, the flat roof structure also serves directly
as a ceiling for the living spaces below (Fig. 11) thereby
facilitating direct transfer of heating and cooling for the spaces
below. In colder climes, where heating is more desirable, attic
ponds under pitched roof glazing are effective. Winter heating
occurs when sunlight heats the water, which then radiates energy
into the living space as well as absorbs heat within the water
thermal mass for nighttime distribution. During the summer, a
reverse process, described later, occurs. For best effect, roof
ponds must be insulated (movable) so that heat will not radiate and
be lost to the outside. One of the major advantages of this approach
is that it allows all rooms to have their own radiant energy source
with little concern about the orientation of the structure or
optimal building form.
 |
Figure 11. Heating cycle -
Roof pond collects and stores heat during the day. At night
roof ponds are covered and stored heat is radiated into the
space below. |
ISOLATED
GAIN
Finally,
the isolated gain design approach uses a fluid (liquid or air) to
collect heat in a flat plate solar collector attached to the
structure. Heat is transferred through ducts or pipes by natural
convection to a storage area - comprised of a bin (for air) or a
tank (for liquid), where the collected cooler air or water is
displaced and forced back to the collector (Fig. 12).
 |
Figure 12. Water or air
convection loop. |
If
air is used as the transfer medium in a convection loop, heated air
coming from the collector is usually directed into a rock (or other
masonry mass material) bin where heat is absorbed by the rocks from
the air. As the air passes its heat to the rocks it cools, falls to
the bottom of the bin and is returned to the collector completing
the cycle. At night the interior space of the structure is heated by
convection of the collected radiant energy from the rock bin. If
water is the transfer medium, the process works in much the same way
except that heat is stored in a tank, and as hot water is
introduced, cooler water is circulated to the collector. In
naturally occurring convection systems (non-mechanically assisted)
collectors must be lower than storage units, which must be lower
than the spaces to be heated (RT). Of
course, the addition of distribution assisting equipment can allow
for placement of system elements anywhere, but that would then be an
Active Solar System.
*PASSIVE
SOLAR HEATING DESIGN CONSIDERATIONS:
SITE
CONSIDERATIONS
(top)
The
performance of any solar energy building, especially one of a
passive design, is strongly impacted by the site and the siting of
the building in relation to its surroundings. During the winter, the
north side of a building receives little direct solar impact due to
shading from the winter sun, which is low in the sky, while the
south side is exposed to the benefits of winter sun exposure. If
site conditions are restricted, the passive solar heated building
location will be the area that receives the most sunlight between
the hours of 9:00 a.m. and 3:00 p.m. during the winter months. The
building location should be near at northern extremity of the sunny
area so that future development on properties to the south will not
block access to winter sunlight. This location also allows open
space for winter activities or gardens to be exposed to as much
winter sun as possible.
BUILDING
SHAPE AND ORIENTATION
(top)
Generally,
buildings oriented along an east-west axis are more efficient for
both winter heating and summer cooling (RT).
This orientation allows for maximum solar glazing (windows) to the
south for solar capture for heating. This orientation is also
advantageous for summer cooling conditions since it minimizes
east-west exposure to morning and afternoon summer sunlight. This
does not mean that all buildings must be rigidly shaped oriented.
Different building shapes and orientations can be designed to
perform efficiently by combining effective glazing, solar exposure,
and shading into the building form. This efficiency can be enhanced
by variations in the placement of interior spaces and by the use of
such options as clerestories and skylights. Depending upon the site,
topography, and shape of the available space, orientations other
than east and west may be desirable. However, for most climates, an
east-west axis is the most efficient for both heating and cooling.
NORTH
WALLS
(top)
In
an east-west oriented building, a north facing exterior wall will
receive little sunlight during the winter and this will be a major
source of heat loss since heat always moves toward cold.
Additionally, building shading of north side open space usually
renders it unusable for outdoor use. To alleviate these situations
the building should be shaped so that the roof slopes downward from
the south to the north wall. This reduces the height of the north
face of the building and therefore the area through which heat is
lost. This also allows sunlight to reach more area of north side
outdoor spaces. Variations of reducing heat loss conditions manifest
in north walls include backing the building into a sloped hillside
or providing a berm, both of which reduce the exposed north area.
Both of these measures accomplish the purpose of a south to north
downward sloping wall (Fig. 13).
 |
| Figure 13. South to north
downward sloping roof reduces heat loss from the north wall
and allows sunlight to reach north side open space. |
INDOOR
SPACE PLANNING
(top)
With
location, orientation and shape of the building is the consideration
of interior space distribution. Habitable spaces that are most
occupied and have the greatest heating and lighting requirement
should be arrayed along the south face of the building. Rooms that
are least used (closets, storage areas, garages) should be placed
along the north wall where they can act as a buffer between high use
living space and the cold north side (Fig. 14).
 |
| Figure 14. Interior space
should be arranged so that rooms with high heating and
lighting requirements are arrayed along the south wall. |
ENTRYWAYS
(top)
Entries
account for great deal of heat loss especially in small structures.
Heat is lost during opening and closing of doors (or windows). Heat
can also be lost by seeping between the doorframe and the door, and
at windows. This kind of window, door or other wall penetration heat
loss (or heat gain in the summer) is called infiltration. To
reduce both direct and infiltration losses, entryways should be
recessed or protected against the direct force of prevailing winds.
Additional loss reduction can be accomplished by providing an
enclosed interior "air lock" space between an entrance
door and the main building. This double entry, or vestibule, creates
a tempered zone between the outside elements and the interior living
space thereby reducing the amount of warm air lost (and summer heat
gained). It also reduces the amount of cold or warm air entering the
living space when the interior door is opened.
WINDOWS
(top)
The
major expanse of windows in a passive solar energy structure will be
south facing solar windows. Whole design planning should include
considerations re: the impact of heat gain in the summer; views;
natural lighting; and privacy requirements in determining the
placement and size of windows in the structure.
For
the most part, window areas on east, west and north facing walls
should be kept as small and as minimal as is consistent with
interior requirements and should be recessed and all should be
double-glazed. Windows are the least effective heat flow inhibitors
of a building's shell, both in terms of letting heat out in the
winter, and letting heat in the summer. When the outside temperature
is 30°F and the inside temperature is 68°F, a square foot of
single pane glass will lose 20 times as much heat (about 43 BTU's
per hour) as a square foot of standard wood frame wall with 3'/z
inches of insulation.
DIRECT
GAIN DESIGN
(top)
SOLAR
WINDOWS
(top)
For
Direct Gain heating the area of the glazed collecting surface is
determined in response to the duration and severity of winter
temperatures; the building size; and the amount of interior thermal
storage mass. A correct balance between these factors must be found
in order to avoid large daily temperature fluctuations that could
result in overheating, even in the winter. As a rule (assuming the
correct amount of thermal storage mass), 0.19 to 0.38 square feet of
south facing glass for each square foot of interior floor area will
provide enough sunlight to maintain an average temperature between
65°F and 70°F during the winter months in cold climates (average
winter temperatures between 20°F and 30°F). In more moderate
climes the same temperatures can be achieved with 0.11 to 0.25
square feet of south facing glass (average winter temperatures
between 35°F and 40°F). More precise data is given in Table 3.
Location and sizing of glazing is also dependent upon the building
layout and types of spaces i.e., frequently used spaces vs.
infrequently used spaces. Adjustments in glazing size and location
of solar windows can occur by the use of reflectors, or when other
passive solar design elements are used in combination with a direct
gain system such as heat loss reduction by the use of movable
insulation, double glazing, and by using wooden sash and frames. The
lower heat conductivity of wood can reduce the heat loss around
windows by as much as 20 percent.
CLERESTORIES
AND SKYLIGHTS
(top)
Earlier
it was mentioned that there may be considerations that override the
need for a large expanse of south facing windows in passive heating
designs. One is that interior room layout may affect the distance
between the collecting windows and the interior thermal storage mass
wall. Thermal storage masses in direct gain designs must receive
direct sunlight impact, and the farther away from the collecting
surface they are, the taller the collecting surface (glazing) must
be in order to have sufficient surface solar contact because of the
sun's angle. This situation may produce intolerable glare and
overheating. Usually, storage walls should not be set back more than
1.25 to 1.5 times the height of the collecting surface - i.e. an
interior thermal storage wall should be no more than 12' from the 8'
tall solar collecting glazing wall. Also, direct sunlight may impact
materials - i.e. dry out wood furniture; discolor certain fabrics;
etc. so care should be taken re: interior decorating and
maintenance. Finally,
and most important, adjacent structures and/or vegetation may reduce
the amount of direct sunlight to the point that a south facing
collecting surface at ground level becomes infeasible or seriously
reduced.
Any
one, or combination of these conditions make south wall heat
collection for direct gain problematic, but can be easily mitigated
by the use of clerestories or skylights. Both of these features
admit sunlight at the roof structure of a building and can be used
to direct sunlight to a specific interior surface. They can also be
used in combination with or as a supplement to a south facing glazed
wall. Additionally, they provide for natural light applications,
which can reduce the need and cost of artificial lighting.
Clerestories
are vertical south facing windows located at roof level (Fig. 15).
Their advantages are that they allow diffuse lighting into a room;
they provide privacy; and they can be placed almost anywhere on a
roof. In a compartmentalized building layout, each room can have its
own source of heat and light. They should be located at a distance
from a thermal storage wall that allows direct sunlight to hit the
wall throughout the winter. This distance is roughly 1.5 times the
height of the wall. Ceilings in rooms containing clerestories should
be light in color to reflect or diffuse sunlight into the living
space. Large interior
spaces may have multiple clerestories arranged to allow maximum
admission of sunlight. Care must be taken that they do not shade
each other, so the clerestorey roof angle (from horizontal) of each
clerestorey should be roughly the same angle of the sun at its
lowest winter point (noon on December 21).
Skylights are simply openings in a roof, which admit sunlight
-they are either horizontal (a flat roof) or pitched at the same
angle as the roof slope. In most cases. horizontal skylights are
used with reflectors to increase the intensity of solar radiation
(remember the angle of incidence). Large skylights should be
provided with shading devices to prevent heat loss at night and heat
gain during the summer months (Fig. 16).
|

|

|
| Figure 15. Clerestory -
clerestories can be used to provide sunshine onto interior
walls which would normally not have a clear view of winter
sunlight. |
Figure 16. Skylights provide
an alternative for direct solar gain, shading devices must be
included as an integral part of the skylight to prevent
overheating the space during mild periods. |
STORING
HEAT – MASONRY
(top)
The
major concern in designing a direct gain passive solar structure to
avoid uncomfortable temperature fluctuations over the day-night
cycle. It is relatively easy to calculate the amount of heat that
will be admitted to a room by any particular collecting surface. It
is not, however, easy to predict the percent of that heat which will
be stored. Since the difference between heat gained and heat stored
will largely determine the temperature fluctuation over a 24-hour
period, this is one of the most important design considerations.
About 65 percent of all heat gained through solar windows during a
clear winter day can be lost during the night. This means that
during the day, 65 percent of the heat gained must be stored to
offset nighttime losses, and to maintain a relatively even
temperature profile. Furthermore, efficient storage during the day
prevents the build-up of heat during daylight hours.
In
general terms, the following rules should be observed in regard to
design of heat storage systems:
*
masonry and concrete floors, walls and ceilings to be used for heat
storage should be a minimum of 4 inches thick.
*
sunlight should be distributed over as much of the storage mass
surface as possible by using translucent glazing. * a number of
small windows to admit sunlight in patches gives better control re:
overheating.
*
use light colored surfaces (non-thermal mass storage walls,
ceilings, floors) to reflect sunlight to thermal storage mass
elements.
*
thermal storage mass elements (floors, walls, ceilings) should b
dark in color.
*
masonry floors used for thermal mass should not be covered with
wall-to-wall carpeting.
*
direct sunlight should not hit dark colored masonry for long periods
of time.
Storing
heat can be accomplished in many ways but the most favorable storage
occurs when each square foot of sunlight is spread (diffused) over a
nine square foot area of storage surface. With this distribution of
sunlight the storage mass need not be more than 4 inches thick. If
sunlight is distributed over less area, storage efficiency can be
increased somewhat by increasing the thickness of the storage mass-
up to eight inches in thickness. Increasing thickness beyond 8
inches has no beneficial effect on heat storage efficiency.
Therefore, the most efficient way to increase heat storage capacity
is to increase the storage surface area and the distribution of
sunlight rather than the thickness of the storage mass. This is
because masonry absorbs heat slowly, and intense sunlight on a small
area will have a negative affect by increasing room temperature
while not significantly increasing the rate heat is absorbed by the
storage mass, while a system using dispersed, less intense radiation
across a larger surface of thermal mass storage will moderate room
temperature fluctuations and store most heat at the same time.
The
heat retention efficiency of masonry storage masses is also
influenced by the kind of masonry used. Table 4 shows that magnesium
brick has twice the conductivity of the other materials listed.
Higher conductivity means that a material responds more quickly in
both absorbing and giving up heat - a quality that increases storage
efficiency and decreases temperature fluctuations.
 |
| Table 4. Thermal storage
material properties. |
INTERIOR
WATER WALLS
(top)
Because
of the material's good convective properties, interior walls of
water (water walls) are much more efficient for thermal collection,
storage, and re-radiation than are masonry walls. Water walls should
be a dark color to increase heat absorption when exposed to direct
sunlight, and will perform well without the problem of heat build-up
in the room. The convection process carries heat away from the
storage surface quickly, preventing heat build-up, and allows the
storage mass to heat evenly in a relatively short time. Widely
fluctuating interior temperatures are not often a problem when
interior water walls are used for heat storage.
If
interior water walls receive direct sunlight between the hours of
10:00 a.m. and 2:00 p.m. and are
a dark color, about one cubic foot of water is required for
each square foot of solar window to maintain comfortable
temperatures during winter
months. Increasing the volume of water in this ratio to 3 cubic fed
of water will decrease daily temperature fluctuations by as much as
6°F.
INDIRECT
GAIN DESIGN:
(top)
Properly
sized, indirect gain thermal storage elements, usually walls, can
provide a high percentage of the heat required to keep a space at
comfortable temperatures, even in very cold climates. Thermal
storage walls, like interior storage walls, can be constructed of
either masonry or water. For masonry walls, between 0.43 and 1.0
square feet of south facing double glazed solar window is needed for
each square foot of floor area in climates with average winter
temperatures between 20°F and 30°F A smaller area can be used
(0.31-0.85) if water is the storage medium. In climates where the
average winter temperature is 35-F to 45°F, the figures are 0.22 to
0.6 for masonry walls and 0.16 to 0.43 for water walls. Table 5
gives more precise information.
 |
| Table 5. Sizing a thermal
storage wall for different climatic conditions. |
THERMAL
STORAGE WALL SIZE
(top)
Correct
wall size varies with local conditions and climate; the amount of
insulation used; and the latitude of the building site. The first
two elements affect the rate of temperature loss from a space, which
is influenced by the amount of difference between outside and inside
temperatures; and how much insulation is used to slow that rate. Latitude is important because it affects the amount of solar
radiation received at the collecting surface on any particular day.
For instance, on a clear January day in Tulsa, Oklahoma, a square
foot of collecting surface will intercept 1883 BTU's while on the
same day, a like amount of surface located in Seattle will intercept
only 1537 BTU's (assuming the same slope for both surfaces). Local
conditions aside, it is generally true that wall size will need to
be increased as one moves further north in latitude.
Other
conditions that bear on wall size include obstructions to solar
radiation exposure, such as trees, structures, etc.. While
unhampered solar access will determine an optimal wall size, reduced
or variable access to the sun will require a larger wall area to
compensate for reduced solar impact. Sizing guidelines identified
herein are based on providing enough heat on a clear January day to
maintain an average space temperature of 65 to 75°F over a 24-hour
period. Since thermal storage walls are placed between the solar
collecting glazing and the interior space to be heated, overheating
is less problematic than with a direct gain design. Very cold
climates, or where site conditions allow less than recommended wall
size, can benefit from the use of reflectors, which bounce the sun's
rays to the collection window, thereby increasing the amount of
solar radiation moving through the glazing and intercepted by the
energy absorber wall. Thermal wall size reduction can occur by as
much as 15% if substantial insulation is used at all other wall and
roof locations to reduce heat loss from the the building.
WALL
DETAILS
(top)
Aside
from the wall area and amount of exposure, the thickness, type of
material, and exposed surface color of a wall are main
considerations that determine the effectiveness of a wall in meeting the thermal needs of the structure's
occupants. In general, cold climate design benefits from dark,
exterior surface colors at the thermal storage wall.
A
variation of the cold climate, indirect gain masonry wall,
which relies on absorption of solar energy at its face and radiation
of converted heat at its back, is the addition of vents at upper and
lower wall locations to provide convected heat to the interior
space. Thermal storage wall vents take advantage of the excessive
heat build up between the glazing and the surface of the storage
wall (Table 7) which can easily exceed 100°F. Venting the top and
bottom of the wall of the living space allows trapped heated air to
move, rising (hot air is lighter than cold air) from the space
between the glazing and wall and flowing into the building interior
through upper vents. As warm air moves through the vents, cooler
room air is drawn through the lower vents, where it is warmed and
rises to repeat the action. This convective cycle directly
warms the interior space at the same time heat is being absorbed by
the thermal mass of the wall, which will give up its heat to the
interior at a later time. This dual action is a benefit for direct
heating as well as delayed heating.
 |
|
| Table 6. Material and
recommended thickness.
|
|
 |
|
| Table 7. Effect of wall
thickness on space air temperature fluctuations. |
|
Convection
can continue 2 to 3 hours after sunset due to the heated exterior
surface of the thermal storage wall, so it is important that upper
vents are closed when the exterior surface begins to cool. This
action prevents a reverse convection cycle, which removes heat from
the space. Interior space heating quality can be controlled by
providing a movable reflective screen across part or all of the
exterior surface of the thermal wall. Vent sizing is about two
square feet for each 100 square feet of thermal wall wall surface,
equally distributed between top and bottom vents (Fig. 17).
 |
Figure 17. Masonry wall - Vent
placement and sizing in mass wall should be as shown in the
illustration. |
Appropriate
wall thickness varies with the material used (Table 6). Again, the
idea is to provide comfortable conditions while avoiding large and
rapid temperature fluctuations. Table 7 gives an idea of the range
of temperature fluctuations for six different wall thicknesses
constructed of five different materials. Regardless of the material
used, it can be expected that while thick walls will produce both
minimum and maximum temperatures at different times of day than thin
walls, due to the
additional time it takes heat to be conducted, their increased
capacity for assimilating and radiating heat will be much greater .
Water
walls are slightly more efficient than masonry walls in collection,
retention and re-radiation of heat. They require different design
consideration i.e. containing the water in an effective, inexpensive
and esthetically pleasing way. There are a variety of water encasing
systems ranging from manufactured, elegant free standing cylinders
and containers to do-it-yourself systems of used, stacked drums,
free-standing plastic cylinders, and site-built tanks.
ATTACHED
GREENHOUSES
(top)
An
indirect gain heating system, using a green house structure as a
heat collector, is multi-purpose, practical and efficient. It also
requires the most rigorous design because of its multiple nature,
which affects sizing for space heating, creating ideal conditions
for greenhouse conditions, and accurately predicting performance for
both. The attachment of a greenhouse to the south side of a building
enables the structure to benefit from the normal, heat collecting
greenhouse operation. The greenhouse collects heat due to its solar
exposure. This heat can be conducted through a thermal storage wall
separating house and greenhouse, or can be convected to the interior
space of the building. In this way the greenhouse serves both as a
heat collector, and a solarium for people and plants. Generally, in
cold climates, a greenhouse design would use between 0.65 and 1.5
square feet of south facing double glass greenhouse collecting
surface for each square foot of floor area in the adjacent living
space. In more moderate climates this can be reduced to 0.33 and 0.9
square feet. This should provide enough heat to keep the average
temperature in the adjacent space between 60°F and 70°F. More data
are given in Table 8.
 |
|
| Table 8. Sizing the attached
greenhouse for different climatic conditions. |
|
It
is desirable for a solar greenhouse structure to be recessed into
the south facade of the building, thereby minimizing east and west
exposures, which have little effect on heat collection but can be a
great source of heat loss. Furthermore, heat transfer through the
common wall between the greenhouse and the living space is increased
in this configuration (Fig. 18). Greenhouses for heating purposes
can be added to frame buildings to provide for direct heat during
winter days, but such buildings, without thermal storage mass, do
not have the ability nor capacity to store heat for use at night.
Some designs integrating greenhouses, adjust for nighttime heating
by transfer of all greenhouse heat to main building storage mass
(floors, walls, etc.) for deferred use at night. This only works in
moderately cold climates, because very cold climates require the
residual heat collected by the greenhouse to keep it, and its
contents, from freezing at night.
The
common wall between the greenhouse and the building interior can be
constructed of thermal mass materials (masonry, water, etc.). The
greenhouse side of common walls should be dark in color (better
absorber) and should receive maximum sunlight throughout the day.
Wall vents and/or operable windows can be used to allow heated air
directly into the interior space during the daytime.
Wall
thickness should be same as that provided for in an indirect gain (Trombe)
wall. If water is used, its minimum thickness should be 8 inches (or
0.67 cubic feet for each square foot of south-facing glass).
Masonry
walls cannot absorb and transfer heat as fast as a greenhouse can
collect it. As a result, temperatures in the greenhouse will
fluctuate as much as 60°F on a clear day. To dampen (level out)
these fluctuations, extra storage mass (such as masonry units or
containers filled with water) can be placed in the greenhouse. These
act as an interior heat dampening water wall (1 cubic foot of water
for each square foot of south facing glass will reduce temperature
fluctuations 25°F to 29°F).
If
water is used as the common wall between the greenhouse and the
living space, temperature fluctuations will be smaller, and if more
than the 0.67 cubic feet of water for each square foot of glass is
used in the wall, temperature fluctuations will be further reduced.
In
cold climates, it may be advantageous to utilize a heat storage, in
the form of a rock bin, under the building or living space, which
would act as thermal storage of heat collected during the day. Heat
transfer can occur by natural convection if the building is terraced
up a slope, or by use of a fan, which would transfer heat to a rock
bed located in a crawl space under the floor of the structure (Fig.
19). The rock bed should spread across 75 to 100% of the floor area
of the structure in cold climates, and 50 to 75% of the floor area
in moderate climates. Heat from the greenhouse should be directed
over the rock bed and a means of returning cold air from the bottom
of the rock bed to the greenhouse should be provided. If a terraced
design is used, colder air will naturally settle due to the
convective loop cycle. About 1.5 to 3 cubic feet of fist-sized rock
is necessary in cold climates and .5 to 1 cubic feet in temperate
climates. Rock bin storage has also been used as a part of a cooling
system in warmer climes.
 |
|
 |
| Figure 18. By extending the
end walls of an attached greenhouse, loss to the outside is
reduced while the heat gains to the space are incresed. |
|
Figure 19. Small fans (less
than 0.25 H.P.) can be used to aid in the transfer of heat
from collection space to more remote parts of the structure. |
ROOF
PONDS
(top)
Roof
ponds can be used both for heating during the winter months and for
cooling during the summer months. In this section only the heating
aspects of roof ponds will be discussed. Table 9 gives the ratios of
roof pond collecting surface for each square foot of floor area in
the interior space. It should be understood that this will vary
depending on location, exposure and local conditions. The lower
ratio given in the table should be adequate at lower latitudes while
the higher ratio should be used at higher latitudes (colder
climates). For latitudes higher that 36° north, roof ponds require
greater solar gain exposure as well as greater protection from loss
of gained heat.
 |
Table 9. |
The
system is simple in concept. The roof pond approach brings the
differing building aspects of a building - roof, ceiling, heating (and cooling) system, and heat
distribution (does away with ducts) into one system. The roof ponds
of contained water are the heating (and cooling) unit. The
roof/ceilings of the building act as the structural support for the
roof ponds; the "radiator" device for evenly distributed
heating of the spaces below; and as a waterproof roof system
providing protection from the elements. The movable insulation above
the ponds is the weather protection, heating/cooling system
"manager" and additional protection from the elements.
Wintertime heating is comprised of daytime opening the insulating
roof layer to allow solar radiation to heat the water beds; water
bed warming heats the supporting structure which is also the ceiling
for spaces below; heated support structure radiates heat to the
space. At night the insulated roof panels close to contain heat
gathered by the ponds to continue heating the spaces below. Cooling
strategies, discussed later, are the opposite operation plus
additional elements.
The
sun in northern latitudes is at a lower angle with solar radiation
traveling through a greater mass of atmosphere, which reduces its
energy content by scattering and reflection. In this situation,
increased area of exposure or use of solar reflection can be used to
increase roof pond effectiveness. Additionally, in colder climates,
the roof pond system benefits from insulating covers to prevent
nighttime losses. The most beneficial insulation system is one that
is multi-purpose and movable,
operating only twice a day to 1) expose the ponds for heat
collection, and 2) to cover the ponds to prevent heat loss at night.
This
insulation system is also beneficial in the summer when the roof
ponds must be insulated to prevent summer heat gain. The movable
insulation structure can operate in a number of ways - rolling,
hinged, etc.. In climates where snow is likely, ponds can be placed
in a solar attic below the sloping roof with south facing glazing to
allow solar gain, and the attic ceiling can be painted o a
reflective color or sheathed with a reflective material. To increase
system performance, glazing for cold climate solar ponds can be dual
pane, or the ponds can contain an upper layer inflated air cell.
Ceiling
structural support for solar ponds (64#/cu. ft.) include structural
metal decking (excellent for thermal transfer to spaces below) or
thin reinforced concrete decks (more costly, less effective for
direct transfer of heat).
In
constructing the support structure for roof ponds, the clear span
can be as much as 16 - 20 feet or more (for metal decking or
reinforced concrete), requiring intermediate structural beams and
supports depending on the layout of the interior space and the
weight of the ponds and insulating devices. This can be a
complicated matter and it is recommended that assistance be sought
from a structural engineer prior to design.
It
is important to provide a waterproof layer (membrane, etc.) at the
pond support system surface to provide protections during draining
of water for maintenance, and from water bed material failure and/or
weather impacts. The
capability to drain the ponds in an easy and non-damaging manner is
important. The water should be enclosed in ultra-violet light
inhibiting (prevents degradation) plastic bags, waterproof
structural metal or fiberglass tanks which form the ceiling below.
The top of the water containment system must be transparent and the
sides/bottom a dark color. Insulation panels should be constructed
so that they can be tightly sealed when closed to prevent
infiltration heat loss. In some applications insulating panels can
also serve as reflectors when open in order to direct more solar to
the ponds.
Heat
is transferred from the roof ponds through the support deck to the
interior space below. The edges of the deck should be carefully
insulated to reduce heat loss. The underside of the support deck
serves as an interior ceiling, and all surfaces (including
galvanized metal decking) should be painted. Because the system
provides a "radiant" ceiling it is important that no
insulation is used
between the root pond and the interior space. The one exception to
this rule is at the bathroom, which generates high humidity from
showers and tubs. Here, an uninsulated ceiling can result in
condensation and drippage, so effective water barriers and
insulation are critical.
Thermal
ponds are typically water filled (6 to 12 inches deep) clear,
ultraviolet inhibiting plastic bags. Care should be taken to choose
materials which do not degrade when exposed to sunlight and water,
nor are easily damaged from handing and local conditions.
Temperature stratification in the ponds is avoided by using a clear
top and dark bottom. With this configuration, sunlight will
penetrate the water, be absorbed at the black surface and heat from
the bottom will cause a continual convection cycle effect in the
pond.
Finally,
exposed pond tops should be sloped to drain. This avoids heat loss
caused by evaporative cooling of the ponds during. While not a
problem for waterbed "bags", this is a problem for more
fixed types of installations. (see
Haggard, K., et al., "Research Evaluation of a System of
Natural Air Conditions." National Technical Information
Service, Springfield, VA 22161, Order Number PB-243498).
Insulating
panels can take many forms and configurations depending on local
conditions and design (flat roof with exposed ponds in temperate and
desert settings; pitched roof with glazing in snow country), and
range from pivoting panels to horizontal, sliding panels constructed
from standard metal building construction systems - insulation of
polyurethane foam reinforced with fiberglass strands between
aluminum skins placed within standard or easily formed metal frames.
Panel tracks and supports must be designed so that the panel system
(insulation and frames) fit
as tightly as possible when closed in order to prevent compromise of
the systems effectiveness. Without an effective seal system a great
deal of heat stored can be lost at night due to infiltration. .
COMBINING
SYSTEMS
(top)
Many
times it is desirable, or even necessary, to use more than one
passive heating design strategy. For instance, the use of a thermal
storage wall may block a beautiful view while a direct gain design
in the same south wall may create intolerable glare and have a
tendency to overheat. In such cases the two designs can be used side
by side or in any other configuration (a thermal storage wall on
each side of a direct gain window). It is essential, however, to
properly size this combination in order to maintain quality control
and avoid undesirable temperature fluctuations. About 60 to 75% of
the energy striking the collecting surface of a direct gain window
can be used in space heating. On the other hand, only about 30 to
45% of the energy striking the collecting surface of a thermal
storage wall is transferred to the interior space as heat. It can be
seen that the approximate ratio in sizing this combination would be
one square foot of direct gain window equals two square feet of
thermal storage collecting surface. With these approximations in
mind, it should be a relatively easy matter to size various
combinations of passive solar designs.
Variation
of roof pond designs make it impossible to present a simple rule of
thumb for integrating with other design approaches. However, by
reviewing the sizing techniques for the other systems and by knowing
the specific design of the roof pond system, an approximate ratio
can be calculated.
CLOUDY
DAY STORAGE
Even
on cloudy days passive solar heating designs continue to collect
energy from diffused sunlight. However, this greatly reduced and
diffuse solar radiation usually does not provide enough energy to
keep interior temperatures at 70°F. Well designed thermal mass
systems are sized to have carryover capacity and when combined with
some auxiliary heating systems, provide for a comfortable
environment for a number of cloudy days.
As
a rule, direct gain systems can provide comfortable conditions for
1-2 cloudy days if the collecting area is increased by 10-20%, and
the interior walls and floors are of solid masonry more than 8
inches thick. If water walls are used in place of masonry, increase
the amount of water to two or three cubic feet for each square foot
of south facing collecting area.
In
climates where a number of consecutive sunny winter days are common
there is a concern for overheating. For example, average
temperatures with the above sizing may result in average interior
temperatures of 74°F. However,
on cloudy days, if the interior temperature drops an average of four
degrees per day, comfortable conditions can be maintained for two
days with no additional heating needed.
Oversizing
in very cloudy or foggy climates is not recommended since thicker
masonry takes a few days of sunshine to become fully charged. In
climates such as these, overly thick storage masses are likely to
result in under-heating problems. Glazed areas with minimum mass
thickness should be used so that the system can respond quickly when
sun is available.
Indirect
gain systems differ slightly when designing for one or two cloudy
days' storage. The collector area should be increased by 10 to 20%,
and thermal storage walls of greater conductivity be used. If water
walls are used, one or more cubic feet of water should be used for
each square foot of collector area.
In
indirect designs, if standard masonry wall material is used for
cloudy day storage., the
surface area of the wall should be increased instead of increasing
masonry wall thickness. This
may increase average daily temperatures, but overheating is easily
mitigated by use of insulating panels or curtains drawn across the
interior of the wall to provide temperature control. Built in
ventilation systems can be used to control overheating for both
indirect gain and direct gain systems..
MOVABLE
INSULATION
In
all structures, the greatest amount of heat gain is lost through
glazing, either by conduction through the glass or by infiltration
around the window frame. All heat loss during the winter reduces the
efficiency of all heating systems including passive solar design,
and where possible, movable, tightly sealed insulation should be
used to cut losses to a minimum. The extent of heat loss under
varying conditions of protection is given in Table 10.
 |
| Table 10. Conduction losses
through single and double glazing with and without shutters
for Boston1. |
The
use of movable insulation can simply involve manually operated
panels that slide on a track across the glazed area, or be motor
driven and temperature activated (more expense but more consistent
control). Mechanical systems can be used to operate insulation
difficult to reach manually. If the building is unattended when
insulation should be moved, automatic timers connected to
thermostats and/or light sensitive devices can operate, providing
appropriate operation of the system. Some machinations can include
automatically operated louvers, motor driven panels (roof ponds,
etc.) and movable insulation. Whatever the method used, an effective
insulation system will greatly increase the efficiency of passive
solar designs.
REFLECTORS
FOR PASSIVE SOLAR HEATING
(top)
If
partial shading is problematic, collection of solar radiation can be
greatly enhanced by the use of reflecting devices.
Generally, horizontal reflector equal in width and one to two
times the height of the glazed opening in. length should be used for
vertical (wall) glazing. South sloping skylights, benefit from
reflectors located above the skylight at a tilt angle of roughly 100°
from the slope of the roof (Fig. 20). The reflector should be
roughly equal to the length and width of the skylight. Solar
collection can be increased 30-40% when reflectors are used with
either vertical, horizontal, or sloping glazing. For greatest
efficiency, the angle of a reflector in relation to the collecting
surface must be carefully selected. Table 11 gives the proper
reflector angle for skylights with varying degrees of slope.
In
some instances, reflecting surfaces can be used to direct sunlight
to an interior storage surface such as a water wall. Reflectors
should also be constructed so that they can be used to block heat
gain in the summer. Table 12 gives the reflecting properties of some
surfacing materials.

Table 11. Reflecting tilt-angles for south-facing skylights. |
|

Table 12. Normal specular solar reflectance
of various surfaces. |
|
SHADING
(top)
South
facing glass can be a source of overheating during summer months.
The potential for overheating can be controlled by a roof overhang
carefully designed to shade the glass during the summer (sun higher
in the sky) but not block sunlight during the winter (lower in the
sky), and by the use of movable outside shading devices.
Overhangs
should be equal in length to roughly one fourth the height of the
window opening in southern latitudes (36° NL) and one-half the
height of the opening in northern latitudes (48° NL).
The
projection of the overhang that will be adequate (provide 100%
shading at noon on June 21) at particular latitudes can be quickly
calculated by using the following formula:
Projection = window opening (height)/ F (see Table 13)
A
slightly longer overhang may be desirable at latitudes where this
formula does not provide enough shade during August.
The
usefulness of overhangs can be increased if they are constructed so
that they are adjustable. Adjustable overhangs can be rolled back to
admit sunlight on cold spring days. Trellised overhangs that support
deciduous vines (vines that lose their leaves in the winter) are
another way to block sunlight in the summer and admit sunlight in
early spring. Retractable awnings and adjustable louvers can also be
useful shading devices.
Table 13. |
|
OUTSIDE
INSOLATION (OUT-SULATION)
(top)
Masonry
wall exterior surfaces can lose large amounts of heat. For example -
to achieve an insulation quality equal to 3.5 inches of
fiberglass insulation, a concrete wall would have to be 12 feet
thick. To avoid masonry wall heat loss to the exterior, it can be
insulated on the outside. This "thermos bottle approach"
includes the walls and the perimeter of foundation walls. Typical
application is the addition of 1 to 2 feet of two-inch rigid
waterproof insulation placed below grade to prevent stored heat in
floors and walls from being lost to the outside.
In
sunny temperate winter climates south facing, dark colored masonry
walls need not be insulated as heat gained during sunny days will
offset nighttime heat loss.
|